DTSD1352-4S Multi-circuit Energy Meter

● Mearsure up to 4 circuit 3 phase
● Mearsure all electric parameters
● Split core open loop CTs
● LCD Display

  • Fast And Safe Logistics
  • Sample Available




General






DTSD1352-4S series DIN-rail type multi-circuit power meter is mainly used for the full electric parametermeasurement of multiple circuits, and can be connected to the current input of 4 three-phase circuits or 12single-phase circuits at the same time. It can measure parameters such as voltage and current, power, power factor,phase angle, unbalance, and harmonics.




Function

Accuracy

Active power: Class 1 

Reactive power: Class 2

Frequency

Range: 45 - 65Hz

Pulse output

Output method:optocoupler pulse with open collector

Power Consumption

≤10VA

Dimension (L*W*H):

Panel size (L×W×H): 87.8*72*71.5 mm

Installation:

Din 35mm

Current:

Overload: 1.2 times rated value (continuous);



Parameter







Auxiliary power
           AC/DC 85~265V; Consumption≤10VA;


Input



Frequency
           45~65Hz;

Voltage

           AC 3×220V/380V; Overload: 1.2 times of rated value (continuous);

           2 times of rated value / 1s; Power consumption: ≤ 0.5VA;each channel)

Current

           Rated value: Secondary input rated current:50mA;Overload: 1.2 times rated value (continuous); 10 times rated value/1 second;power consumption: ≤ 0.5VA(each channel);

Measurement accuracy

           Frequency: 0.05Hz, voltage and current: 0.5 class, active energy: 1 class, reactive energy: 2 class; 2nd to 31st harmonic accuracy: ±1%;



Features

Pulse output
           Output method: optocoupler pulse with open collector,the pulse constant defaults to 400imp/kWh (and active open input can only be either-or.);
Communication
           RS485 interface, Modbus-RTU protocol; baud rate 1200~38400;
Switching Input
           2-way or 4-way passive dry contact input, built-in power supply;
           2-way active wet node input (AC220V), identify the oil generator and mainsaccess (and pulse output can only be either-or.);

Switching Output

           Output method: relay normally open contact output;
           Contact rating: AC 250V/3A DC 30V/3A;


Dimension

Meter (L×W×H)87.8*72*71.5mm

35mm Din rail installation; Tolerance: ±1mm

TypeRatioLine LengthAccuracyInstallation Method
AKH-0.66/W-9NY 50A/20mA50A/20mA(1+0.2)mClass 0.2Closed type, crystal head interface
AKH-0.66/K-Φ10N 50A/20mA50A/20mA(1+0.2)mClass 0.5Open type, crystal head interface
AKH-0.66/W-12NY 100A/50mA100A/50mA(1+0.2)mClass 0.2Closed type, crystal head interface
AKH-0.66/K-Φ16N 100A/50mA100A/50mA(1+0.2)mClass 0.5Open type, crystal head interface
AKH-0.66/W-20Y 200A/50mA200A/50mA(1+0.5)mClass 0.2Closed type, crystal head interface
AKH-0.66/K-Φ24N 200A/50mA200A/50mA(1+0.5)mClass 0.5Open type, crystal head interface
AKH-0.66/W-30NY 250A/50mA250A/50mA(1+0.5)mClass 0.2Closed type, crystal head interface
AKH-0.66/K-Φ24N 250A/50mA250A/50mA(1+0.5)mClass 0.5Open type, crystal head interface
AKH-0.66-TD-Φ60-NY300-1000A/50mA(1+0.5)mClass 0.2Closed type, crystal head interface
AKH-0.66/K-Φ36N 400A/50mA400A/50mA(1+0.5)mClass 0.5Open type, crystal head interface
AKH-0.66/K-Φ36N 600A/50mA600A/50mA(1+0.5)mClass 0.5Open type, crystal head interface








Installation

Wiring

Network

Package




MINIMUM PACKAGE







MINIMUM PACKAGE


Package Dimension(1 PC)

170*150*130mm

Package Weight(1 PC)

0.245Kg


WHOLE BOX PACKAGE


Package Dimension(36 PCS)

540*530*480mm

Package Weight(36 PCS)

10.5kG


PRODUCT HS CODE


9028301400

ATTENTION !

The above packing and weight data are only refer to model DTDS1352-4S.

For other models or optional functions, please contact the salesman for details, thank you for your cooperation!