ADW210 IoT Multi-circuit Energy Meter

ADW210 series multi-loop power meter is mainly used for the measurement of all electric parameters of three-phase circuit. Colleagues can select the current input of the maximum four circuits. ADW2XX series products are connected by split core current transformer, easy to install on site, and realize remote wireless communication through wireless communication module.

  • Fast And Safe Logistics
  • Sample Available

Features

    • Mearsure up to 4 circuit 3 phase
    • Mearsure all electric parameters
    • Split core open loop CTs
    • External function module, such as MK(switching inputs and outputs), MTL(temperature measurement and leakage current measurement), AWT100(wireless communication)
    • LCD Display

Function

Accuracy
Active power: Class 1
Reactive power: Class 2

Frequency
Range: 50 - 60Hz 

Pulse output
Active pulse output and reactive pulse output

Consumption
<0.5VA(Single phase)

Dimension (L*W*H)
Panel size (L×W): 72*97.7*36 mm

Installation: Din 35mm

Wireless
Transmission on 470MHz and maximum distance 
in open space is 1km; 2G; NB

Starting current: 4‰lb

Parameter

Auxiliary power AC/DC 85~265V; Consumption≤10VA;
Input Frequency 45~65Hz;
Voltage AC 3×220V/380V; Overload: 1.2 times of rated value (continuous);
2 times of rated value / 1s; Power consumption: ≤ 0.5VA;
Current AC 5A、100A、400A、600A;(External opening transformer); Power consumption: ≤ 0.5VA;
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s;
Measurement accuracy Frequency 0.05Hz, voltage、current Class 0.5; 2-31st harmonic accuracy: ± 1%;
Active electric energy level 1, reactive electric energy level 2;
Features Pulse output Output mode: optocoupler pulse with open collector;
Communication RS485、Modbus-RTU; Baud rate 1200~38400;
Switching Input Dry contact input、Built in power supply;
Switching Output Output mode: Relay normally open contact output; contact rating: AC 250V/3A DC 30V/3A;

External Module (MTL)

12 External NTC Temp. Measurement
4 Channels Residual Current Measurement

External Wireless Module(AWT100)

Downlink RS485; Uplink 4G, 2G, NB, Lora, LoraWAN, Ethernet, WiFi, GPS, Profibus

External Module(MK)

12 Channels DI + 4 Channels DO

Dimension

Installation

Wiring

① U / Pulse / DO / DI / Communication / Auxiliary Power Supply
② Brand
③ Panel 
④ Model Number 
⑤ CH1, CH2, CH3, CH4 for current / extension module interface
⑥ Button
⑦ Infrared Status
⑧ Pulse Output Light

Network




Package







MINIMUM PACKAGE







MINIMUM PACKAGE


Package Dimension(1 PC)

170*150*130mm

Package Weight(1 PC)

0.245Kg


WHOLE BOX PACKAGE


Package Dimension(36 PCS)

540*530*480mm

Package Weight(36 PCS)

10.5kG


PRODUCT HS CODE


9028301400

ATTENTION !

The above packing and weight data are only refer to model ADW210.

For other models or optional functions, please contact the salesman for details, thank you for your cooperation!