ALP220-EF Earth Fault Relay

● Application: Low-voltage distribution systems (up to 380V)
● Purpose: Provides overcurrent, earth-fault, residual current, unbalance, and short-circuit protection
● Auxiliary Supply: AC/DC 85~265V
● Current Inputs: (4 channels) 1A or 5A (selectable, depending on external CT)
● Current Measurement Range: 10%Ie ~ 1000%Ie
● Measurement Accuracy: ±2%
● Residual Current Input: 30mA~1000mA (requires optional residual current transformer)
● Frequency Range: 45Hz~65Hz, accuracy ±0.2Hz
● Relay Outputs: 2 x SPDT (Form C), resistive load: AC 250V 5A / DC 30V 5A

  • Fast And Safe Logistics
  • Sample Available




General



The ALP220-EF Earth Fault Overcurrent Relay is designed for low-voltage applications (up to 380 V) where it is necessary to monitor the system's ground current and provide protection when the ground current exceeds the permissible limit. This relay features  an  LCD  display,  Modbus-RTU  communication  capability,  system  current  measurement,  three-phase  current overcurrent  protection,  ground  current  overcurrent  protection,  residual  current  measurement,  residual  current  overcurrent protection, fault logging, and event logging functions.
The product complies with the relevant standards:
GB/T 14598.27-2025 "Measuring Relays and Protective Devices – Part 27: Safety Requirements for Products "
GB/T 14598.27-2025 "Measuring Relays and Protective Devices – Part 26: Electromagnetic Compatibility Requirements " GB/T 2423 "Environmental Testing ofElectrical and Electronic Products – Part 2: Test Methods "
RoHS Directive 2.0 (2011/65/EU, (EU) 2015/863)




Technical Specifications

Function Standard configuration Optional
  Measurement Function Three-phase alternating current √  
Neutral conductor current √  
Residual current   √
        Defencive function Inverse-time overcurrent protection √  
Inverse Time Grounding √  
Three-stage time-delayed overcurrent protection √  
Three-stage time-delayed ground fault protection √  
Current imbalance √  
Leakage current   √
Communication Function Modbus-RTU √  
Digital output function 2  Single-pole double-throw switch √  
  Record Function 20 Single fault record √  
20 Event Record
Display Function Liquid-crystal display √  
  Setpoint Setting Function Operation Panel Modification √  
Communication Amendment

Functional Configuration

Dimensions