AMC series meters adopt AC sampling technology, which can measure the current ,voltage,power, power factor and electric energy parameters in the power grid separately. It can set the magnification through the panel membrane switch. The meters have RS485 communication interface, adopt Modbus protocol; also can convert the power signal into a standard DC analog signal.
Communication
RS485(Modbus-RTU)
Display
LCD display, set multiplying power
Rated I
AC current: AC1A, 5A
Accuracy
Active energy: Class 0.5
Installation
Panel mounted
Dimension(L*W*H)
Panel size (L×W): 75*75mm
Cutout(L×W): 67*67mm
Depth (H): 94.3mm
Consumption
Current: Power consumption< 0.5VA;
Auxiliary power supply: power consumption≤5VA
Auxiliary power supply
AC 220V
Technical Datasheet
Technical Parameter | Value | |
Input | Rated Value | AC voltage:Single phaseAC 100V,400V Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96) AC current:AC1A,5A; |
Overload | Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current:1.2 times rated value(continuous); 10 times rated value /1 second | |
Frequency | 45Hz~65Hz | |
Power Consumption | Power consumption of each voltage,current input circuit is less than 0.5VA | |
Accuracy | Class 0.5 | |
Function | Display | LED or LCD |
Communication | RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps etc. | |
Alarm | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. | |
Analog | DC4~20mA,( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output) | |
Switching | Input:4 channel or 2 channel dry contact Input,built in power supply Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC | |
Auxiliary Supply | AC/DC 85-265V | |
Power Consumption | <5VA | |
Insulation resistance | ≥ 100MΩ | |
Power frequency withstand voltage | Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV | |
Environment | Temperature | Operation: -10℃~+55℃Storage: -25°C ~+70°C |
Humidity | ≤95%RH,no condensation,without corrosive gas | |
Altitude | ≤ 2500m |
Package
MINIMUM PACKAGE | ||||
MINIMUM PAKAGE | Package dimensions(1 PC) 170*150*130mm | Pakage Weight(1 PC) 0.62Kg | ||
WHOLE BOX PAKAGE | Package dimensions(16 PCS) 450*245*200mm | Pakage Weight(16 PCS) 3.66kG | ||
PRODUCT HS CODE | 9028301400 |
ATTENTION ! The above packing and weight data are only refer to model AMC72L-AI. For other models or optional functions, please contact the salesman for details, thank you for your cooperation! |