BM200 Isolated Safety Barrier

BM200 isolated safety barrier can transmit signals between the safe area and the dangerous area, and limit the energy transfer from the safe area to the dangerous area caused by the fault. The voltage, current, temperature, resistance signals generated by the equipment (transmitter) on the dangerous side are isolated and converted into corresponding linear voltage and current signals outputting to the safe area. The product requires independent power supply, and the input/output/power supply is isolated. It can be used in current source, two-wire, three-wire transmitter equipment.

  • Fast And Safe Logistics
  • Sample Available

BM200-DI/I-B11

      • Input: 0~20mA /4~20mA
    • Output: 0~20mA /4~20mA (Safe side input); Load resistance: ≤550Ω
    • Powered 20~35V DC
    • 35mm Din rail installation

Features

① DC voltage/current input
② Using magnetic isolation technology
③ Response time <400ms
④ TS35 rail installation
⑤ Plug-in terminal
⑥ Temperature drift coefficient: ≤200ppm/℃ at 0.5 level

Parameter




Channel type

Single-way input and single-way output, single-way input and double-way output, double-way input and double-way output

Input type

                 Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple

 Input signal

                 0~20mA /4~20mA

                 0~5V /0~10V /1~5V (Distribution voltage: 12V/20mA) PT100 /0~10K/KETJ

                 NRSB

 Output signal

          0~20mA /4~20mA (Safe side input); Load resistance: ≤550Ω 0~5V /1~5V (Safe side

          input); Load resistance: ≥330K

          0~10V (Safe side input); Load resistance: ≥500K

Transmission accuracy

                 0.2%

Temperature modulus

                 50ppm/℃ (The output signal is current)

Response time

                 5ms to reach 90% of final value

                (RTD Pt100/resistance/thermocouple input: 1s to reach 90% of final value

Power supply

                20~35V DC

Work temperature

                -20℃+60℃

Fix mode

                Rail installation


 Dielectric strength

               Intrinsically Safe and Non-Intrinsically Safe ≥2500V AC; Power supply and Non-           

               Intrinsically Safe ≥500V AC

               NoteIntrinsically Safe is input, Non-Intrinsically is output

Dimension

Structure

Application










Oil
Chemical Industry
Pharmaceutical
Metallurgy




Package








MINIMUM PACKAGE







MINIMUM PACKAGE


Package dimensions(1 PC)

17*15.5*12.5cm

Package Weight(1 PC)

0.2Kg


WHOLE BOX PACKAGE


Package dimensions(10 PCS)

45.5*26*19.5cm

Package Weight(10 PCS)

3kG


PRODUCT HS CODE


9030339000

ATTENTION !

The above packing and weight data are only refer to model BM-AI/IS.

For other models or optional functions, please contact the salesman for details, thank you for your cooperation!