AM3SE Middle Voltage Protection Relay

● A complete set of protection, related to the application;
● 3 current input, 3 voltage input, 11DI, 5DO;
● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V, DC48V, DC24V;
● 1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU;
● 1 GPS for GPS timing;
● More than 200 sequence of event records, more than 400 system logs, and more than 10 seconds tripping context records;
● Powerful graphic programmable Logic.

  • Fast And Safe Logistics
  • Sample Available


General


AM3SE series microcomputer protection device integrates protection and control, and is suitable for user terminal substations (stations) of 35kV and below voltage level. Application areas cover electric power, water conservancy, transportation, petroleum, chemical, coal, metallurgy and other industries.







LCD Display









Function


Protection functions

AM3SE-


I

U

Overcurrent (3 stages,IDMT)


Earth fault (3 stages,IDMT)(I01/I02)


Negative sequence overcurrent (2 stages,IDMT)


Auto-reclose


Overload (trip/alarm)


Under frequency


Post-accelerated overcurrent


Post-accelerated overcurrent(I01/I02)


Overvoltage(trip)


Undervoltage (trip)


Self-produced over zero-voltage (trip)


Residual overvoltage (trip)


FC block


Trip and close circuit supervision (alarm)


Non-electricity (trip/alarm)


Undervoltage (alarm)

Overvoltage (alarm)

Residual overvoltage (alarm)

Over frequency


Voltage phase loss protection


PT supervision (alarm)

Self-produced over zero-voltage (alarm)


Rear ports

I

U

RS485

Protocols

I

U

Modbus serial

IEC 60870-5-103

Measurement

I

U

Electric parameter

U,I,P,Q,PF,Fr,Ep,Eq,Es

Input Current

5

0

Input Voltage

3

3

Logs and Records

I

U

Fault recorder

Sequence of event record

Monitoring Functions

I

U

Anti-pumping circuit

Optional


Remote control



Wiring

Connection

FAQ




Q: How to set the CT and PT ratio of the protection device?

A:The protection device can set the CT and PT ratio through the fixed value menu. For example, the current transformer is 75/5 and the voltage transformer is 10/0.1, then the CT ratio is set to 15 and the PT ratio is set to 100.



Q: How to distinguish the model when place order of AM3SEthat a single line protection and transformer protection?

A: A AM3SE is suitable for circuit protection and transformerprotection. No need to distinguish between models when placing orders.



Q: When the voltage is three-phase three-wire system, does the current have to be connected with 2CT?

A: The voltage wiring mode and current wiring mode of the protection device can be set independently, and can be connected freely.



Q: How to confirm whether the anti-trip function is configured?

A: If the circuit breaker is equipped with anti-trip, the device does not must be equipped with anti-trip; if the circuit

breaker does not have anti-trip, you need to configure the AM5-FT anti-trip module. (If DC48V is selected as the

operating power supply, the anti-trip box is not optional, and the circuit breaker must be equipped with anti-trip

function; if you choose AC anti-trip, please note that AC and DC general anti-tripping)



Q: How to purchase suitable protection devices?

A: Before ordering, it is recommended to consult related engineers, select the appropriate protection model,

and then fill in the corresponding selection table, and place the order after confirmation by the engineers.